Troubleshooting Guide: What to Do If Your 3 Ton R-32 AC Isn’t Cooling (or Heating) Right
Tony Marino’s Step-by-Step Fixes Before You Call the Pros
🧠 Tony’s Intro: “Don’t Panic — Diagnose”
Every summer, I get the same call.
“Tony, my AC’s running, but it’s not doing anything.”
Nine times out of ten, it’s something small — a dirty filter, a tripped breaker, or a drain switch.
The truth is, most “failures” aren’t failures. They’re symptoms.
So before you shell out $300 for a service call, here’s my field-tested troubleshooting checklist for your 3 Ton Goodman R-32 system — written the same way I train new techs in the field.
We’ll walk through electrical, airflow, refrigerant, thermostat, and drainage issues — everything that keeps your system from cooling or heating right.
⚙️ 1. Know Your System Basics
If you own a Goodman GLXS4BA3610 condenser with the AMST36CU1300 air handler, it runs on R-32 refrigerant, rated around 14.5 SEER2.
That means you’ve got a high-efficiency, single-stage unit designed for about 36,000 BTU of cooling — enough for 1,400–1,800 sq ft of space.
Understanding that helps you diagnose like a pro:
-
Compressor runs at full capacity (not variable).
-
The blower uses an ECM motor that adjusts speed automatically.
-
Cooling relies on R-32’s smooth thermodynamic flow — leaks or clogs hit performance fast.
(Goodman MFG R-32 Specifications)
👉 Tony’s Take:
If your system’s not cooling, think air, refrigerant, or power. It’s always one (or a combo) of those three.
🔌 2. Step One — Check Power Supply
No power, no cooling. Simple.
a. Check the Thermostat
-
Make sure it’s set to Cool and the temperature is below room temperature.
-
Replace batteries (if it uses any).
-
If the screen is blank, pull the cover and check for 24 V from the control board.
b. Check the Breaker Panel
-
Find the AC and Air Handler breakers (two separate circuits).
-
Flip each fully off, then back on.
c. Check the Outdoor Disconnect
-
Pull the disconnect fuse block. If burnt or melted, replace with an identical rating (typically 30–40 A).
👉 Tony’s Tip:
If you reset the breaker and it trips again immediately — that’s not a fixable DIY issue. That’s a short or failing capacitor.
💨 3. Step Two — Airflow: The Silent Killer
About 70 % of “not cooling” complaints come down to airflow.
a. Check the Filter
Pull it out. If it looks like felt instead of mesh, replace it.
A clogged filter drops airflow, freezes the coil, and makes you think the system’s “low on freon.”
b. Check Supply & Return Vents
All vents should be open and unblocked.
Don’t close unused rooms — it increases static pressure and cuts cooling power.
c. Check for Ice on the Coil
If you see frost or ice:
-
Turn the system OFF.
-
Set thermostat to Fan Only.
-
Let it thaw for 2–3 hours.
Then check the filter again.
👉 Tony’s Field Rule:
“Airflow problems look like refrigerant problems until you actually measure pressure.”
🧊 4. Step Three — Check Temperature Split
Run the AC for 10 minutes, then measure the air temperature:
Location | Normal Range | What It Means |
---|---|---|
Return grille | 75 °F – 80 °F | — |
Supply vent | 55 °F – 60 °F | — |
Difference (ΔT) | 16 – 22 °F | Normal operation |
If ΔT is under 14 °F → airflow or refrigerant issue.
If ΔT is over 25 °F, → restricted airflow (dirty coil, blower, or filter).
👉 Tony’s Trick:
You can use a $20 infrared thermometer — no gauges needed.
🧯 5. Step Four — Drainage and Float Switch
Your air handler’s condensate pan has a float safety switch. When the drain clogs, it cuts power to save you from water damage.
(Energy Star Condensate Maintenance)
How to Reset:
-
Locate the PVC drain pipe near the air handler.
-
Pull the cleanout cap and pour 1 cup of vinegar or bleach mix.
-
Wait 30 minutes, then reset the thermostat.
👉 Tony’s Tip:
If it happens again soon, install a secondary drain or condensate pump — you’ve got a slope issue.
⚡ 6. Step Five — Capacitors and Contactors
If your outdoor fan hums but doesn’t spin, or the compressor won’t start:
It’s likely a failed capacitor or pitted contactor.
Symptom | Suspect | Quick Check |
---|---|---|
Humming, fan not spinning | Run capacitor | Push fan blade (if it starts, cap’s bad) |
Clicking, no startup | Contactor | Check for 24 V coil voltage |
👉 Tony’s Warning:
These store power — discharge with a resistor, not a screwdriver. If you don’t know how, stop and call a pro.
🧰 7. Step Six — Refrigerant Issues (When It’s Time for Gauges)
R-32 is a single-component refrigerant, so charge accuracy is crucial.
Too much = high head pressure; too little = coil freeze.
Signs you might be low on charge:
-
Bubbling or hissing at the evaporator.
-
Frost line halfway up the suction pipe.
-
Low ΔT (< 14 °F).
👉 Tony’s Rule:
Only an EPA-certified tech can legally measure or recharge R-32.
If you suspect a leak, turn it off and call service — running low risks of compressor damage.
🔥 8. Step Seven — If It’s Not Heating (for Heat Pump Systems)
Some 3 Ton R-32 setups include a heat pump or electric heat kit.
If you’re getting cold air in heating mode:
a. Check Mode
Set thermostat to Heat, fan to Auto.
b. Check Outdoor Unit
If the fan isn’t spinning or frost covers the coil → defrost failure.
c. Check Auxiliary Heat
If strips don’t engage, the breaker or sequencer could be bad.
(Energy.gov Heat Pump Operation Guide)
👉 Tony’s Take:
If you hear it click but no heat output, odds are your defrost board or outdoor sensor is the culprit.
🌬️ 9. Step Eight — Blower Problems
If the outdoor unit runs but no indoor air blows:
Problem | Likely Cause | Fix |
---|---|---|
Blower silent | Tripped breaker | Reset, test voltage |
Blower hums only | Bad motor capacitor | Replace |
Blower cycles erratically | ECM motor or control board | Tech diagnosis |
👉 Tony’s Field Note:
ECM motors are sensitive — voltage drops or dirty filters kill them faster than anything. Use a surge protector.
💡 10. Step Nine — Thermostat Communication
Smart thermostats sometimes lose connection or “forget” settings.
-
Reboot the device.
-
Re-link to Wi-Fi.
-
Verify R and C wires are tight.
If the thermostat clicks but the outdoor unit doesn’t start, check 24 V at the Y terminal — no voltage = blown low-voltage fuse on the control board.
(Energy Star Smart Thermostat Troubleshooting)
👉 Tony’s Tip:
Always use the right transformer size (40 VA minimum for Wi-Fi thermostats).
🧊 11. Step Ten — Icing and Defrost Cycles
R-32 systems run slightly cooler discharge temps. In humid climates, coils may frost overnight.
If it happens:
-
Set the fan to On for 30 minutes to thaw.
-
Check that the defrost sensor (if a heat pump) is attached to the coil.
👉 Tony’s Advice:
If it freezes often, airflow is too low, or the charge is off. Don’t just keep thawing — fix the cause.
💧 12. Step Eleven — Duct Leaks
If one room’s hot and another’s freezing, it’s likely duct leaks or disconnected runs.
Check attic or crawlspace:
-
Look for collapsed flex ducts.
-
Seal with mastic (not tape).
-
Replace uninsulated runs.
👉 Tony’s Take:
A single 2-inch gap can lose 20 % of airflow. That’s the silent money leak no one sees.
🔋 13. Step Twelve — Static Pressure
Too much static pressure = blower strain + poor cooling.
Your tech should measure it (under 0.7 in WC ideal).
If you hear “whooshing” or “howling” vents, the static’s too high.
👉 Tony’s Tip:
Add a return vent or wider filter grille to breathe easier — it’s the cheapest airflow upgrade.
🧱 14. Step Thirteen — Noise Diagnosis
Every sound means something:
Noise | Likely Issue | Severity |
---|---|---|
Hiss | Refrigerant leak | ⚠ |
Buzz | Contactor coil | ⚙ |
Rattle | Loose panel | 🧰 |
Squeal | Blower bearing | 🚨 |
Pop | Duct expansion | Normal |
👉 Tony’s Note:
If noise changes overnight, don’t ignore it — early fixes prevent compressor damage later.
🧾 15. Step Fourteen — Control Board & Fuses
Your air handler control board has a small 3–5 A blade fuse.
If your thermostat screen is blank and the outdoor unit won’t engage, check that first.
👉 Tony’s Trick:
Use a spare automotive fuse — same rating, same size.
🧰 16. Step Fifteen — When to Call a Pro
Call for service if:
✅ Breaker trips repeatedly
✅ Coil keeps freezing
✅ Refrigerant hiss continues after shutdown
✅ Compressor won’t start, but the fan does
✅ Drain pan overflows
👉 Tony’s Guideline:
If you’ve done steps 1–10 and it’s still misbehaving — that’s a refrigerant, control, or mechanical issue. Time for gauges, meters, and experience.
💬 17. Tony’s Quick-Fix Story
One of my Florida clients thought her compressor died mid-July.
Turns out a frog had wedged itself into the contactor.
Two minutes, one small critter relocation, and the “broken” system was as good as new.
👉 Moral:
Not every no-cool is catastrophic. Always check the obvious before the expensive.
💡 18. Preventive Moves After You Fix It
Task | Frequency | Benefit |
---|---|---|
Filter change | 1–2 months | Airflow stability |
Coil rinse | 2× year | Lower head pressure |
Drain flush | 3 months | Prevent float trips |
Annual tune-up | 1× year | Keeps warranty valid |
👉 Tony’s Rule:
Every $1 spent on maintenance saves $4 in repair.
🌎 19. R-32-Specific Tips
R-32 is mildly flammable (A2L), but safe when installed correctly.
If you smell a faint “sweet chemical” odor or hear a hiss:
-
Shut off the power.
-
Ventilate.
-
Call a licensed R-32 technician.
👉 Tony’s Note:
Never use leak sealant chemicals — they gum up expansion valves.
🏁 20. Tony’s Final Word
Your 3 Ton R-32 air conditioner is a precision machine — and 80 % of problems can be fixed with basic maintenance and a few minutes of attention.
Whether it’s a tripped float switch or a bad capacitor, you can save serious time and money by learning to diagnose the basics before calling in backup.
👉 Tony’s Bottom Line:
“Don’t fear your AC — learn its language. Every sound, every frost patch, every click means something.”
Do your part with airflow, cleanliness, and good power — and your R-32 system will return the favor every hot summer day for the next two decades.
Next, Tony will compare the Top 3 ton R-32 brands.