Troubleshooting Guide: What to Do If Your 3 Ton R-32 AC Isn’t Cooling (or Heating) Right

Troubleshooting Guide: What to Do If Your 3 Ton R-32 AC Isn’t Cooling (or Heating) Right

Tony Marino’s Step-by-Step Fixes Before You Call the Pros


🧠 Tony’s Intro: “Don’t Panic — Diagnose”

Every summer, I get the same call.

“Tony, my AC’s running, but it’s not doing anything.

Nine times out of ten, it’s something small — a dirty filter, a tripped breaker, or a drain switch.
The truth is, most “failures” aren’t failures. They’re symptoms.

So before you shell out $300 for a service call, here’s my field-tested troubleshooting checklist for your 3 Ton Goodman R-32 system — written the same way I train new techs in the field.

We’ll walk through electrical, airflow, refrigerant, thermostat, and drainage issues — everything that keeps your system from cooling or heating right.


⚙️ 1. Know Your System Basics

If you own a Goodman GLXS4BA3610 condenser with the AMST36CU1300 air handler, it runs on R-32 refrigerant, rated around 14.5 SEER2.

That means you’ve got a high-efficiency, single-stage unit designed for about 36,000 BTU of cooling — enough for 1,400–1,800 sq ft of space.

Understanding that helps you diagnose like a pro:

  • Compressor runs at full capacity (not variable).

  • The blower uses an ECM motor that adjusts speed automatically.

  • Cooling relies on R-32’s smooth thermodynamic flow — leaks or clogs hit performance fast.

(Goodman MFG R-32 Specifications)

👉 Tony’s Take:
If your system’s not cooling, think air, refrigerant, or power. It’s always one (or a combo) of those three.


🔌 2. Step One — Check Power Supply

No power, no cooling. Simple.

a. Check the Thermostat

  • Make sure it’s set to Cool and the temperature is below room temperature.

  • Replace batteries (if it uses any).

  • If the screen is blank, pull the cover and check for 24 V from the control board.

b. Check the Breaker Panel

  • Find the AC and Air Handler breakers (two separate circuits).

  • Flip each fully off, then back on.

c. Check the Outdoor Disconnect

  • Pull the disconnect fuse block. If burnt or melted, replace with an identical rating (typically 30–40 A).

👉 Tony’s Tip:
If you reset the breaker and it trips again immediately — that’s not a fixable DIY issue. That’s a short or failing capacitor.

(NFPA Electrical Safety Code)


💨 3. Step Two — Airflow: The Silent Killer

About 70 % of “not cooling” complaints come down to airflow.

a. Check the Filter

Pull it out. If it looks like felt instead of mesh, replace it.
A clogged filter drops airflow, freezes the coil, and makes you think the system’s “low on freon.”

(Energy Star Filter Guide)

b. Check Supply & Return Vents

All vents should be open and unblocked.
Don’t close unused rooms — it increases static pressure and cuts cooling power.

c. Check for Ice on the Coil

If you see frost or ice:

  1. Turn the system OFF.

  2. Set thermostat to Fan Only.

  3. Let it thaw for 2–3 hours.
    Then check the filter again.

👉 Tony’s Field Rule:
“Airflow problems look like refrigerant problems until you actually measure pressure.”


🧊 4. Step Three — Check Temperature Split

Run the AC for 10 minutes, then measure the air temperature:

Location Normal Range What It Means
Return grille 75 °F – 80 °F
Supply vent 55 °F – 60 °F
Difference (ΔT) 16 – 22 °F Normal operation

If ΔT is under 14 °F → airflow or refrigerant issue.
If ΔT is over 25 °F, → restricted airflow (dirty coil, blower, or filter).

👉 Tony’s Trick:
You can use a $20 infrared thermometer — no gauges needed.


🧯 5. Step Four — Drainage and Float Switch

Your air handler’s condensate pan has a float safety switch. When the drain clogs, it cuts power to save you from water damage.

(Energy Star Condensate Maintenance)

How to Reset:

  1. Locate the PVC drain pipe near the air handler.

  2. Pull the cleanout cap and pour 1 cup of vinegar or bleach mix.

  3. Wait 30 minutes, then reset the thermostat.

👉 Tony’s Tip:
If it happens again soon, install a secondary drain or condensate pump — you’ve got a slope issue.


⚡ 6. Step Five — Capacitors and Contactors

If your outdoor fan hums but doesn’t spin, or the compressor won’t start:
It’s likely a failed capacitor or pitted contactor.

Symptom Suspect Quick Check
Humming, fan not spinning Run capacitor Push fan blade (if it starts, cap’s bad)
Clicking, no startup Contactor Check for 24 V coil voltage


👉 Tony’s Warning:
These store power — discharge with a resistor, not a screwdriver. If you don’t know how, stop and call a pro.


🧰 7. Step Six — Refrigerant Issues (When It’s Time for Gauges)

R-32 is a single-component refrigerant, so charge accuracy is crucial.
Too much = high head pressure; too little = coil freeze.

Signs you might be low on charge:

  • Bubbling or hissing at the evaporator.

  • Frost line halfway up the suction pipe.

  • Low ΔT (< 14 °F).

👉 Tony’s Rule:
Only an EPA-certified tech can legally measure or recharge R-32.
If you suspect a leak, turn it off and call service — running low risks of compressor damage.


🔥 8. Step Seven — If It’s Not Heating (for Heat Pump Systems)

Some 3 Ton R-32 setups include a heat pump or electric heat kit.
If you’re getting cold air in heating mode:

a. Check Mode

Set thermostat to Heat, fan to Auto.

b. Check Outdoor Unit

If the fan isn’t spinning or frost covers the coil → defrost failure.

c. Check Auxiliary Heat

If strips don’t engage, the breaker or sequencer could be bad.

(Energy.gov Heat Pump Operation Guide)

👉 Tony’s Take:
If you hear it click but no heat output, odds are your defrost board or outdoor sensor is the culprit.


🌬️ 9. Step Eight — Blower Problems

If the outdoor unit runs but no indoor air blows:

Problem Likely Cause Fix
Blower silent Tripped breaker Reset, test voltage
Blower hums only Bad motor capacitor Replace
Blower cycles erratically ECM motor or control board Tech diagnosis

👉 Tony’s Field Note:
ECM motors are sensitive — voltage drops or dirty filters kill them faster than anything. Use a surge protector.


💡 10. Step Nine — Thermostat Communication

Smart thermostats sometimes lose connection or “forget” settings.

  • Reboot the device.

  • Re-link to Wi-Fi.

  • Verify R and C wires are tight.

If the thermostat clicks but the outdoor unit doesn’t start, check 24 V at the Y terminal — no voltage = blown low-voltage fuse on the control board.

(Energy Star Smart Thermostat Troubleshooting)

👉 Tony’s Tip:
Always use the right transformer size (40 VA minimum for Wi-Fi thermostats).


🧊 11. Step Ten — Icing and Defrost Cycles

R-32 systems run slightly cooler discharge temps. In humid climates, coils may frost overnight.

If it happens:

  • Set the fan to On for 30 minutes to thaw.

  • Check that the defrost sensor (if a heat pump) is attached to the coil.

👉 Tony’s Advice:
If it freezes often, airflow is too low, or the charge is off. Don’t just keep thawing — fix the cause.


💧 12. Step Eleven — Duct Leaks

If one room’s hot and another’s freezing, it’s likely duct leaks or disconnected runs.

Check attic or crawlspace:

  • Look for collapsed flex ducts.

  • Seal with mastic (not tape).

  • Replace uninsulated runs.

👉 Tony’s Take:
A single 2-inch gap can lose 20 % of airflow. That’s the silent money leak no one sees.


🔋 13. Step Twelve — Static Pressure

Too much static pressure = blower strain + poor cooling.

Your tech should measure it (under 0.7 in WC ideal).

If you hear “whooshing” or “howling” vents, the static’s too high.

👉 Tony’s Tip:
Add a return vent or wider filter grille to breathe easier — it’s the cheapest airflow upgrade.


🧱 14. Step Thirteen — Noise Diagnosis

Every sound means something:

Noise Likely Issue Severity
Hiss Refrigerant leak
Buzz Contactor coil
Rattle Loose panel 🧰
Squeal Blower bearing 🚨
Pop Duct expansion Normal


👉 Tony’s Note:
If noise changes overnight, don’t ignore it — early fixes prevent compressor damage later.


🧾 15. Step Fourteen — Control Board & Fuses

Your air handler control board has a small 3–5 A blade fuse.
If your thermostat screen is blank and the outdoor unit won’t engage, check that first.

👉 Tony’s Trick:
Use a spare automotive fuse — same rating, same size.


🧰 16. Step Fifteen — When to Call a Pro

Call for service if:
✅ Breaker trips repeatedly
✅ Coil keeps freezing
✅ Refrigerant hiss continues after shutdown
✅ Compressor won’t start, but the fan does
✅ Drain pan overflows

👉 Tony’s Guideline:
If you’ve done steps 1–10 and it’s still misbehaving — that’s a refrigerant, control, or mechanical issue. Time for gauges, meters, and experience.


💬 17. Tony’s Quick-Fix Story

One of my Florida clients thought her compressor died mid-July.
Turns out a frog had wedged itself into the contactor.
Two minutes, one small critter relocation, and the “broken” system was as good as new.

👉 Moral:
Not every no-cool is catastrophic. Always check the obvious before the expensive.


💡 18. Preventive Moves After You Fix It

Task Frequency Benefit
Filter change 1–2 months Airflow stability
Coil rinse 2× year Lower head pressure
Drain flush 3 months Prevent float trips
Annual tune-up 1× year Keeps warranty valid


👉 Tony’s Rule:
Every $1 spent on maintenance saves $4 in repair.


🌎 19. R-32-Specific Tips

R-32 is mildly flammable (A2L), but safe when installed correctly.
If you smell a faint “sweet chemical” odor or hear a hiss:

  • Shut off the power.

  • Ventilate.

  • Call a licensed R-32 technician.

👉 Tony’s Note:
Never use leak sealant chemicals — they gum up expansion valves.


🏁 20. Tony’s Final Word

Your 3 Ton R-32 air conditioner is a precision machine — and 80 % of problems can be fixed with basic maintenance and a few minutes of attention.

Whether it’s a tripped float switch or a bad capacitor, you can save serious time and money by learning to diagnose the basics before calling in backup.

👉 Tony’s Bottom Line:

“Don’t fear your AC — learn its language. Every sound, every frost patch, every click means something.”

Do your part with airflow, cleanliness, and good power — and your R-32 system will return the favor every hot summer day for the next two decades.

Next, Tony will compare the Top 3 ton R-32 brands.

Tony’s toolbox talk

Leave a comment

All comments are moderated before being published