Maintenance Checklist:
How Mike Keeps Weil-McLain Cast-Iron Boilers Running for 25+ Years**
The Truth: Cast Iron Doesn’t Die of Old Age — It Dies From Neglect
Let me cut straight to the point:
**A Weil-McLain CGA-5 isn’t a “15-year boiler.”
It’s a 25–35 year boiler — IF you maintain it the Mike way.**
Cast-iron boilers don’t have delicate aluminum exchangers.
They don’t have fragile sensors that die when the moon is in the wrong phase.
They don’t rely on a computer to breathe.
They rely on:
-
combustion stability
-
draft stability
-
clean water
-
proper pressure
-
adequate circulation
-
correct temperature rise
-
minimal air entrainment
If ANY of those go sideways, the boiler suffers.
If ALL of those are kept in line, it becomes the hydronic equivalent of a diesel locomotive.
This is EXACTLY how Mike keeps CGA-5 boilers running long after newer “high efficiency” boilers have hit the scrap pile.
1. Annual Combustion Test — The Heartbeat of the Boiler
I don’t care if the flame “looks good.”
Your eyes cannot measure:
-
CO
-
CO₂
-
O₂
-
flue efficiency
-
draft stability
-
excess air
-
burner alignment
Combustion needs an analyzer.
The [Flame Efficiency Diagnostic Sheet] shows that combustion drifts 2–6% per year on atmospheric boilers due to:
-
burner dust
-
orifice fouling
-
gas pressure variance
-
chimney temperature swings
If you don’t tune the flame annually:
-
efficiency drops
-
soot builds
-
flue temperatures fall
-
condensation increases
-
chimney decay accelerates
A CGA-5 with a bad flame is a car with a clogged carburetor — it will run, but badly.
2. Clean the Burners and Pilot Assembly — Small Dirt = Big Problems
Atmospheric burners are simple, but not magic.
Dust, lint, rust flakes, and spider webs (yes, spiders LOVE gas burner tubes) cause:
-
lazy flame
-
yellow tips
-
high CO
-
delayed ignition
-
popping sounds
-
rumble on startup
The [Burner Tube Airflow Restriction] confirms that partially blocked burner tubes increase CO output by up to 300%.
Every year:
-
remove burner tray
-
vacuum dust
-
brush burners lightly
-
clean pilot orifice
-
check thermocouple position
-
tighten pilot hood
-
confirm stable flame
This takes minutes and prevents thousands in repairs.
3. Verify Draft & Chimney Operation — The Silent Boiler Killer
Draft problems destroy atmospheric boilers faster than anything.
Poor draft causes:
-
CO spillage
-
pilot outages
-
burner instability
-
condensation in flue
-
rust flakes dropping into burners
-
soot buildup
-
chimney mortar failure
The [Chimney Draft Degradation and Seasonal Flow Report] shows draft weakens significantly in:
-
cold chimneys
-
oversized flues
-
blocked liners
-
negative pressure basements
Every inspection MUST include:
-
draft test with instrument
-
visual flue check
-
chimney cap inspection
-
connector slope verification
-
spillage test at draft hood
If your installer doesn’t test draft?
They’re not a boiler tech.
4. Flush the Low-Water Cutoff (LWCO) — The Device That Saves Your Boiler’s Life
Cast-iron boilers crack when run dry.
That’s why the LWCO exists.
But if the LWCO isn’t flushed?
It:
-
fills with sludge
-
sticks
-
misreads water level
-
fails during emergencies
-
exposes the boiler to dry firing
The [Sludge Contamination Bulletin] shows LWCOs in older systems begin sticking after just 6 months of sludge accumulation.
Every heating season:
-
check LWCO
-
flush until water runs clear
-
test life-saving shutdown
-
verify electrical response
This is NON-NEGOTIABLE.
5. Expansion Tank Check — The #1 Cause of Relief Valve Leaks
A dead expansion tank turns your system into a pressure bomb.
Symptoms:
-
relief valve dripping
-
boiler pressure rising to 30 psi
-
fluctuating temperature
-
noisy pipes
-
spitting air vents
The [Hydronic Pressure Stabilization and Air Removal Log] confirms over 80% of pressure issues come from failed diaphragm tanks.
Check annually:
-
tap tank — hollow = good, solid = waterlogged
-
measure pressure charge (12 psi cold)
-
check Schrader valve for leaks
-
inspect tank orientation (must be vertical)
Replace tanks that fail pressure checks immediately.
6. System Water Quality — The Hidden Cause of 75% of Cast-Iron Failures
Cast iron is tough, but NOT invincible.
Bad water causes:
-
magnetite sludge
-
corrosion
-
blocked radiators
-
circulator damage
-
uneven heating
-
boiler hot spots
The [Cast-Iron Corrosion Pattern Ledger] reveals that untreated boiler water accelerates internal casting wear by 30–50%.
Every year:
-
test pH (should be 8.0–9.0)
-
test hardness
-
check for iron oxide
-
confirm water clarity
-
flush if contaminated
-
add inhibitor if needed
Water is the lifeblood of hydronics.
Treat it with respect.
7. Bleed Air & Purge Zones — Air Is the Enemy of Circulation
Air causes:
-
cold radiators
-
cavitating circulators
-
banging pipes
-
reduced flow
-
high return temps
-
low heat output
The [Air Migration and System Entrapment Behavior Field Note] shows that air re-enters older systems constantly, especially in:
-
multi-story homes
-
homes with panel radiators
-
systems with long returns
Every fall:
-
purge each zone
-
bleed radiators
-
confirm auto-vent operation
-
check air separator condition
Air sneaks in constantly — removing it is ongoing maintenance.
8. Check Circulators & Zone Valves — The Real “Weak Links” of the System
CGA-5 boilers rarely fail.
Circulators and zone valves fail all the time.
The Hydronic Component Stress & Annual Wear Pattern Chart found:
-
circulators average 8–12 years
-
zone valves average 7–10 years
-
actuator motors fail far earlier
During annual maintenance:
-
verify pump amperage
-
check bearings
-
check flow checks
-
listen for cavitation
-
test zone valve motors
-
test end switches
-
confirm proper opening/closing
A dead circulator can make a perfectly good boiler look “broken.”
9. Inspect the Pressure-Reducing Valve (PRV) & Backflow Preventer
Your system pressure should be:
-
12–18 psi (cold)
-
18–25 psi (hot)
If pressure is drifting?
Your PRV is sticking.
If your PRV sticks open?
You flood the system.
You blow relief valves.
You crack radiators.
If it sticks closed?
Your boiler runs dry.
The Backflow & Feed Valve Reliability Analysis shows PRVs begin drifting after 5–7 years, especially in hard-water homes.
Annual testing is mandatory.
10. Clean the Boiler Sections — Flush Out Soot & Improve Heat Exchange
Even atmospheric boilers accumulate:
-
soot
-
rust flakes
-
scale
-
combustion debris
These insulate the cast-iron sections, reducing heat exchange.
The Cast-Iron Section Temperature Stress Behavior Ledger confirms section fouling increases metal stress by raising surface temperature differentials.
Every maintenance cycle:
-
vacuum flue passages
-
brush heat exchanger
-
inspect removable draft hood
-
check section alignment
Clean cast iron = cool cast iron = long-lived cast iron.
11. Test All Safety Controls — They MUST Work Every Time
A CGA-5 has:
-
high limit control
-
low-water cutoff
-
spill switch
-
roll-out switch
-
draft safety
-
gas valve safety circuit
These protect the boiler from:
-
overheating
-
dry firing
-
backdraft
-
burner misfire
-
flue blockage
The Boiler Safety Circuit Reliability Verification Record shows annual testing reduces catastrophic failures by 90%.
Do not skip safety testing.
Ever.
12. Mike’s Seasonal Checklist (What He Actually Does)
FALL
✔ Full purge
✔ Pressure charge check
✔ Circulator test
✔ PRV/backflow test
✔ Air separator inspection
✔ Combustion tuning
WINTER
✔ Draft inspection
✔ Pilot flame check
✔ Gas pressure verification
✔ Zone valve cycling
SPRING
✔ Flush LWCO
✔ Water chemistry analysis
✔ Sediment flush
✔ Exchanger brushing
SUMMER
✔ Inspect expansion tank
✔ Inspect chimney
✔ Replace worn gaskets
✔ Inspect gas connections
You don’t get 25+ years by accident — you get it through consistency.
Mike’s Final Verdict — Cast Iron Doesn’t Need Much, But It Needs It EVERY Year
A Weil-McLain CGA-5 can outlive the house it’s installed in, IF you:
✔ Keep the flame clean
✔ Keep the draft stable
✔ Keep the water pure
✔ Keep the air out
✔ Keep the pressure balanced
✔ Keep the circulators moving
✔ Keep the safeties tested
✔ Keep the chimney healthy
Boilers don’t “wear out.”
Boilers are killed by:
-
neglect
-
bad water
-
poor draft
-
dead pumps
-
no maintenance
-
air buildup
Do the maintenance,
and your boiler becomes a 30-year machine.
That’s the Mike way.
In the next blog, we will know the right time to replace your old boiler.







