Fan-Only, Heat, Cool What Startup Mode You Should Begin With and Why

When a PTAC gets powered up for the first time, the biggest mistake isn’t wiring, voltage, or even the thermostat.

It’s starting in the wrong mode.

I’ve watched people flip straight to heat on a cold morning or slam it into cooling because the room feels stuffy. That’s how you turn a clean install into a mystery problem.

Startup modes aren’t about comfort.
They’re about verification.

Each mode tells you something different about the unit, the install, and the power feeding it. If you start in the wrong order, you miss those signals — and you don’t find out something’s wrong until it’s expensive.

This guide explains which startup mode comes first, which comes last, and why skipping steps costs you later.

Amana Distinctions Model 12,000 BTU PTAC Unit with 3.5 kW Electric Heat


🧠 The Core Rule of PTAC Startup Modes

Before we go mode by mode, lock this into your head:

Startup is a diagnostic process — not a comfort test.

You’re not asking the PTAC to heat or cool yet.
You’re asking it: “Are you mechanically and electrically ready to work?”

That’s why the order matters.


🌀 Mode 1: Fan-Only — Always First, No Exceptions

Fan-only mode is the foundation of every proper PTAC startup.

Why fan-only comes first

  • It uses the least electrical load

  • It avoids compressor or heater engagement

  • It verifies airflow and mechanical clearance

  • It exposes shipping damage or install mistakes safely

If something is wrong, fan-only is where you want to find out.

What fan-only mode tells you

When you run fan-only for the first time, you’re checking:

  • Blower spins freely

  • No scraping, ticking, or vibration

  • Airflow is steady and unrestricted

  • No loose hardware inside the cabinet

Run fan-only for at least 10 minutes.

If the unit can’t pass this test quietly and smoothly, do not proceed. Cooling and heating only magnify problems that already exist.

Verified reference:
Amana PTAC Installation & Operation Manual
https://www.manualslib.com/manual/531523/Amana-Ptac.html


🔍 What Happens If You Skip Fan-Only?

Skipping fan-only is how people miss:

  • Shipping brackets left in place

  • Pinched wiring near the blower

  • Sleeve misalignment causing vibration

  • Loose insulation rubbing the fan wheel

These don’t always stop the unit — they just shorten its life and make noise you’ll never fully get rid of later.

Fan-only is your quiet inspection window. Use it.


❄️ Mode 2: Cooling — The Compressor Test

Cooling mode comes second, never first.

By the time you reach cooling:

  • Airflow is confirmed

  • Fan motor is proven

  • Cabinet is stable

Now you’re ready to engage the compressor.

What to expect in cooling mode

  • A short delay before the compressor starts

  • A low, steady hum (not a bang or clunk)

  • Gradual temperature drop

  • No sudden breaker trips

Cooling mode confirms:

  • Correct voltage delivery

  • Compressor health

  • Control board sequencing

  • Refrigerant system integrity

Do not expect instant ice-cold air. PTACs are designed for controlled output, not shock cooling.


🚫 Why Cooling Should Never Be First

Starting in cooling before fan-only risks:

  • Running a compressor with restricted airflow

  • Masking fan vibration under compressor noise

  • Forcing a shutdown before diagnostics are complete

The compressor is the most expensive component in the unit. You don’t “test” it casually.


🔥 Mode 3: Heat — Always Last, Always Deliberate

Heat mode comes last, especially on PTACs with electric heat (3.5 kW).

Why? Because heat mode places the highest electrical demand on the system.

If something is wrong upstream — breaker size, wiring, receptacle quality — heat mode will expose it immediately.

What heat mode confirms

  • Breaker and wiring are properly sized

  • Voltage remains stable under load

  • Heating elements engage correctly

  • Control logic switches safely from cool to heat

When you switch to heat:

  • Fan should engage first

  • Heating elements should energize

  • Air should warm within a few minutes

  • Breaker should hold without nuisance trips

A brief “new heater” smell is normal. Burning, sharp, or persistent smells are not.

Verified reference:
Amana PTAC Electric Heat Overview
https://www.amana-ptac.com/resources


⚠️ Why Heat Mode Exposes Problems Fast

Electric heat doesn’t care about intentions. It pulls real amperage.

Heat mode reveals:

  • Undersized breakers

  • Loose electrical connections

  • Shared circuits that shouldn’t exist

  • Voltage drop under load

That’s why heat is last. You want every other system verified before you stress the electrical side.


🔁 The Correct Startup Mode Order (Always This)

Here’s the order I use — every time:

  1. Fan-Only (10 minutes minimum)

  2. Cooling Mode (observe full cycle)

  3. Heat Mode (confirm load handling)

Change the order, and you lose information you can’t get back.


🚫 Startup Mode Mistakes I See Constantly

These are the most common errors:

  • Starting in heat on a cold day

  • Cycling modes too fast

  • Restarting power during compressor delay

  • Assuming noise is “normal”

  • Ignoring breaker behavior during heat

PTACs don’t fail mysteriously. They fail because the startup sequence was rushed or skipped.


📋 Quick Startup Mode Checklist

Before advancing modes, confirm:

✅ Fan-only runs quietly
✅ Airflow feels consistent
✅ No vibration or rattling
✅ Cooling engages smoothly
✅ Breaker holds under cooling
✅ Heat engages without tripping

If one box isn’t checked, stop there.


🧱 Tony’s Final Word

Startup modes aren’t suggestions — they’re a conversation with the machine.

Fan-only asks, “Can you breathe?”
Cooling asks, “Can you work?”
Heat asks, “Can the building support you?”

Ask those questions in the wrong order, and you won’t like the answers you get later.