So, you’ve installed your Goodman GLXS4BA3610 air conditioner condenser with the AMST36CU1300 air handler, flipped the breaker, and… nothing. Or maybe you hear a humming or buzzing sound but no compressor kick-on. Whether your outdoor unit is dead silent or giving off strange noises, electrical issues are likely the culprit—and ignoring them can snowball into major problems down the road.
In this post, we’ll walk through step-by-step troubleshooting of the most common electrical issues you might encounter during or shortly after installation. If your GLXS4BA3610 isn't working as it should, we’ll help you get to the root of the problem—without unnecessary guesswork.
The Unit Buzzes but Doesn’t Start
A buzzing sound with no fan movement often points to a faulty capacitor or stuck contactor.
-
Check the dual run capacitor: This is a common failure point in outdoor condensers like the GLXS4BA3610. Use a multimeter set to microfarads (µF) to test. If the readings are significantly below the rated values, it's time to replace it. Here's a quick guide on how to test a capacitor.
-
Inspect the contactor: The contactor relays voltage to the compressor and fan motor. If it’s buzzing but not engaging, it could be pitted or stuck. Learn to spot bad HVAC contactors.
The Unit Hums, Then Shuts Off
A humming followed by a click and shutoff often means the compressor is trying to start but can't.
This could indicate:
-
Hard start issues: The compressor may need a hard start kit if it’s struggling to overcome pressure or internal resistance. These are common in older units, but sometimes needed in new installs if voltage drop is present.
-
Low voltage or poor connections: Use your multimeter to check incoming line voltage. A drop below 208V can cause intermittent startup failures. If the wires are loose or corroded, they can’t carry enough current.
For voltage testing best practices, check out this step-by-step tutorial.
Nothing at All? Silent Unit Diagnosis
If the unit is totally silent, and you’ve already checked the breaker, you might have:
-
A tripped disconnect fuse – Test continuity across the fuses in the disconnect box.
-
No call for cooling – Check if the thermostat is actually calling for cooling. If it's not, the 24V signal won’t reach the contactor.
-
Blown low-voltage fuse on the air handler’s control board – The 3-amp fuse may blow due to shorted wiring or improper thermostat connections. For reference, here's a great explainer on how control boards protect your system.
Wiring and Transformer Troubles
The 24V transformer inside the AMST36CU1300 air handler powers the control side of your condenser. If it’s not sending voltage out, your outdoor unit won't respond at all.
-
Confirm 24V between R and C at the control board.
-
If the transformer is dead, you’ll likely need a replacement. Just make sure it matches the original specs.
Want to dive deeper? This comprehensive AC wiring guide can help you trace circuits and diagnose dead spots in control voltage flow.
Final Thoughts: Fix It Right or Call for Help
Whether your GLXS4BA3610 is buzzing, humming, or completely unresponsive, electrical issues shouldn't be taken lightly. Misdiagnosis can lead to component failure—or worse, injury.
If you’ve already ruled out the thermostat, capacitor, contactor, transformer, and fuses—and it’s still not working—it’s time to bring in an expert.
And if you're still deciding whether this system is right for you, check out the full system listing here:
👉 Goodman 3 Ton 14.5 SEER2 System (GLXS4BA3610 + AMST36CU1300)
Stay safe, stay cool—and don’t let a little hum turn into a major headache.
Need more troubleshooting and installation tips for these systems? Visit my guide right here!