Maintenance Checklist for Your Daikin 10 Ton RTU: What to Do Each Season (Tony’s Pro-Level Guide)
A 10-ton rooftop unit is one of the hardest-working pieces of equipment in any commercial building. Whether you’re running a retail store, a small office, a warehouse, a restaurant, or anything in-between, your RTU is the reason your building doesn’t turn into a sauna, a freezer, or a humidity swamp.
But here’s the blunt reality Tony has learned over decades of rooftop crawling:
Commercial HVAC systems don’t fail from “bad luck.” They fail from “bad maintenance.”
And the Daikin 10 Ton 15 IEER2 packaged unit is no different.
Daikin builds tough equipment. Durable equipment. Efficient equipment.
But no rooftop unit is invincible—not when it’s sitting on a roof getting roasted by the sun, blasted by wind, filled with dust, and forced to run for thousands of hours every year.
That’s why a seasonal maintenance checklist isn’t optional.
It’s the difference between:
✔ A 15–20 year lifespan
and
✘ A 7–10 year burnout disaster
Today, I’m giving you the real commercial maintenance plan—Tony style.
Not the watered-down “change your filters” brochure.
The actual checklist your building needs to keep that Daikin running efficiently, quietly, safely, and for as long as possible.
Let’s get into it.
Why Seasonal Maintenance Matters More Than You Think
Most building owners only call HVAC techs when:
-
The AC stops cooling
-
The heat stops heating
-
The unit starts making weird noises
-
Tenants or staff start complaining
-
Utility bills spike
-
Water starts leaking inside
-
Breakers trip
-
Rooftop equipment freezes over
By that time, the damage is often already done.
Commercial rooftop units aren’t complicated when you understand one thing:
“HVAC systems don’t die suddenly. They die slowly, over years, when nobody’s paying attention.”
Coils get dirtier.
Airflow drops.
Belts loosen.
Motors strain.
Economizers malfunction.
Electrical connections burn out.
Refrigerant conditions drift.
And the unit has to work harder to produce the same cooling.
Maintenance is simply reversing that slow death before it becomes a failure.
Here’s a reference for long-term equipment degradation behavior:
[Commercial HVAC Wear & Performance Trends]
Spring Maintenance Checklist (Cooling Season Prep)
Spring is the most important maintenance period of the entire year.
If you skip spring maintenance, you’re gambling with your summer.
Here’s Tony’s complete spring checklist:
1. Clean the Condenser Coil Thoroughly
Not “sort of.”
Not “spray and pray.”
A rooftop condenser coil needs:
-
Foam cleaner
-
Pressure rinse
-
Full fin exposure
-
Debris removal
-
Straightened bent fins
Dirty coils cause:
-
High head pressure
-
Compressor failures
-
Higher energy bills
-
Capacity loss
-
Shortened lifespan
I’ve seen 30% cooling loss from dirty coils. No exaggeration.
2. Inspect & Clean the Evaporator Coil
This one is often overlooked because it’s “inside the unit.”
Don’t ignore it.
Dirty evaporator coils cause:
-
Coil freezing
-
Poor cooling
-
Water overflow
-
Mold growth
-
Reduced airflow
Here’s a coil hygiene concept:
[Evaporator Coil Cleaning Principles]
3. Replace Air Filters
Airflow is life.
A cheap filter is the cheapest insurance policy in HVAC.
Replace filters:
-
Monthly for restaurants
-
Monthly to bi-monthly for gyms
-
Every 2–3 months for offices
-
Every quarter for warehouses
If filters look dirty? Replace immediately.
4. Inspect Fan Motors & Bearings
Problems you’ll catch early:
-
Bearing wear
-
Motor overheating
-
Shaft play
-
Fan imbalance
-
Motor noise
A failing fan motor can drag down efficiency for months before dying.
5. Inspect Belts & Pulleys
A loose or cracked belt causes:
-
Poor airflow
-
Noise
-
Excessive motor strain
-
Fire risk in extreme cases
Replace belts every 1–2 years, or sooner if they squeal.
6. Check Refrigerant Performance (Not Just Pressures)
A good tech checks:
-
Superheat
-
Subcooling
-
Evaporating temperature
-
Condensing temperature
-
Line temperatures
-
Sight lines for oil
-
Compressor amps
Incorrect refrigerant levels quietly destroy compressors over time.
[Refrigerant Performance Evaluation Methods]
7. Inspect Economizer Operation
95% of economizers I’ve checked over the years were not working right.
Check:
-
Damper movement
-
Actuator operation
-
Sensor calibration
-
Outdoor air temperature sensors
-
Minimum position settings
A stuck-open economizer can add tons of extra load.
8. Tighten Electrical Connections
Loose electrical lugs cause:
-
Burned contactors
-
Failed boards
-
Blower shutdowns
-
Compressor damage
-
High resistance that raises amp draw
Tony rule: tighten every screw.
9. Inspect the Roof Around the Unit
A leaking or weak curb can:
-
Damage the building
-
Rot the roof
-
Cause mold growth
-
Destroy the RTU base
Check:
-
Flashing
-
Sealant
-
Curb insulation
-
Attachment points
This is non-negotiable.
Summer Maintenance Checklist (High Load Season)
Summer is where your Daikin earns its paycheck.
The unit will run harder, longer, and hotter than any other time of year.
1. Visual Checks Every Month
Look for:
-
Ice buildup
-
Dirt accumulation
-
Debris blocking the coil
-
Sagging panels
-
Loud noises
-
Uneven cooling complaints
2. Clean the Condenser Coil Again (If Needed)
A mid-summer coil rinse can dramatically improve performance.
I’ve saved restaurants thousands during heatwaves just by rinsing clogged coils.
3. Verify Fan Speeds & Blower Performance
High heat stresses:
-
Blowers
-
Belts
-
Motors
-
Bearings
A weak blower equals weak cooling—period.
4. Measure Delta T (Temperature Split)
Ideal cooling temp split:
18°F–22°F
More?
May indicate restricted airflow.
Less?
May indicate refrigerant issues or coils clogged.
Fall Maintenance Checklist (Heating Prep + End of Cooling Season)
Fall is your chance to fix anything summer damaged.
1. Deep Clean the Coils (Both Sides)
Cooling season dirt piles up—remove it before winter.
2. Furnace Inspection (If Gas Heat)
Check:
-
Burners
-
Flame sensors
-
Igniters
-
Heat exchanger
-
Gas pressure
-
Venting
-
Safeties
Gas issues can be dangerous and costly.
3. Inspect Electrical After Heavy Runtime
Heat expands metal.
Long runtimes cause wear.
Connections loosen.
Fall tightening is essential.
Here’s a seasonal electrical inspection reference:
[HVAC Electrical Fatigue Patterns]
4. Verify Economizer Seal
Winter air infiltration is bad for heating bills.
5. Check The Roof for Damage
Summer storms beat up commercial roofs:
-
Loose flashing
-
Curb lift
-
Sealant cracks
-
Water pooling
Fix roof issues early.
Winter Maintenance Checklist (Low Load + Freeze Protection)
Winter is easier on cooling components but brutal in different ways.
1. Inspect the Heat Exchanger
DANGER zone if cracked:
-
Carbon monoxide
-
Poor heat output
-
Inefficiency
-
Shutdowns
Replace at first sign of cracking.
2. Test Defrost Cycle (If Heat Pump)
A malfunctioning defrost will freeze the coil into a block of ice.
3. Clear Snow & Ice From Around the Unit
Snowdrifts clog airflow.
Ice buildup stresses fan motors.
4. Inspect Drain Pans & Lines
Frozen drains = flooding during thaw cycles.
5. Reduce Fresh Air Intake
Too much outside air = wasted heating energy.
Annual Maintenance (Tony’s Deep-Dive List)
Once per year, your Daikin should get the full inspection, including:
✔ Full coil cleaning
✔ Complete electrical inspection
✔ Refrigerant performance analysis
✔ Duct static pressure test
✔ Motor amperage testing
✔ Fan balancing
✔ Belt replacement
✔ Economizer calibration
✔ Gas pressure tuning
✔ Roof sealing inspection
✔ Drain cleaning
✔ Full airflow measurement
✔ AHU interior cleaning
✔ Panel tightening
✔ Vibration analysis
Here’s an annual-maintenance framework:
[Comprehensive HVAC Annual Inspection Checklist]
This is the difference between 10-year failure and 20-year lifespan.
Signs Your Daikin 10 Ton Unit Needs Immediate Attention
Don’t wait for the building to cook.
If you hear, smell, or see any of these, call for service:
-
Loud rattling
-
Burning smell
-
Weak airflow
-
Ice on lines
-
Water leaking
-
Breaker tripping
-
High humidity
-
Warm supply air
-
Excessive vibration
-
Frequent cycling
-
Abnormal energy spikes
RTUs send warning signs.
Ignoring them is expensive.
Tony’s Final Verdict
If you own a Daikin 10 Ton 15 IEER2 rooftop unit, you’re starting with a solid piece of equipment.
But even the best system can’t survive neglect, bad installation, or airflow problems.
A proper maintenance plan:
✔ Lowers energy bills
✔ Improves comfort
✔ Extends lifespan
✔ Reduces breakdowns
✔ Maintains warranty validity
✔ Lowers operating noise
✔ Improves air quality
✔ Prevents major repairs
Neglect maintenance?
You’ll pay for it three times over:
-
Higher utility bills
-
More frequent repairs
-
Early replacement
In commercial HVAC, you don’t save money by skipping maintenance.
You save money by doing it right.